| | | Rubber antivibration mounts Condenser coil in copper/aluminium with acrylic coating Condenser coil in copper/aluminium with Fin Guard (Silver) treatment Copper/copper condenser coil Serial communication module (MODBUS) Steel mesh filter on water side Room keypad Service keypad (cable from 1,5 metres) Phase monitor Double temperature control kit, set point compensation 4-20 mA, 3-way valve Set point compensation with according to outdoor enthalpy | | |
| | | | | | | | | | | | Sizes | 51 | | | | ► Cooling capacity WSAT-EE | (1) | kW | 12,3 | | | | Total input WSAT-EE | (1)(2) | kW | 4,33 | | | | Total EER at 100% - WSAT-EE | | 2,84 | | | | ESEER - WSAT-EE | | 3,25 | | | | | (3) | kW | 13,6 | | | | Total input | (2)(3) | kW | 4,40 | | | | COP | | 2,89 | | | | Pump working head WSAT-EE | (1) | kPa | 135 | | | | Number of refrigerant circuits | | | | | | Number and type of compressors | (4) | | | | | | Sound pressure level WSAT-EE | (5) | dB(A) | 60 | | | | Power supply | V/Ph/Hz | | | | | | | | | | | | | | | | | | | | | 61 | 71 | 81 | 91 | | | | 14,4 | 16,2 | 18,2 | 21,2 | | | | 5,22 | 5,79 | 6,50 | 8,31 | | | | 2,76 | 2,80 | 2,80 | 2,55 | | | | 3,42 | 3,28 | 3,28 | 3,00 | | | | 16,3 | 18,0 | 20,6 | 24,3 | | | | 5,00 | 5,76 | 6,46 | 8,23 | | | | 3,01 | 2,92 | 3,00 | 2,85 | | | | 131 | 116 | 118 | 97 | | | | 1 | | | | 1 SCROLL | | | | 60 | 60 | 62 | 63 | | | | 400/3/50+N | | | | | | | | | | | | | | | |
| | | (1) Internal exchanger water = 12/7°C; external air temperature 35°C. (2) Total input is obtained from the compressor input + fan input + auxiliary circuit input. (3) Ambient temperature = 7°C (R.H. = 85%); internal exchanger water outlet temperature 45°C. (4) ROT = rotary compressor | | (5) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions. | | |