Product Data OMNIZONE™ 50BV020-064 Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps 18 to 60 Nominal Tons Omnizone 50BV units offer: • Puron® (R-410A) refrigerant • High-boy modular units break down to fit through a standard, 36-in. doorway • Either two or four high-efficiency scroll compressors for efficient part load control, quiet operation and system redundancy • Suction and discharge Schrader valves on manifold gage connections Omnizone 50BV units are self-contained, water-cooled indoor cooling units or water source heat pumps. Flexible, efficient and economical 50BVC,J,Q,Y020-034 SINGLE PIECE OMNIZONE UNIT Units are available for constant volume (CV) or variable air volume (VAV) applications (with the exception of heat pumps) in both modular and singlepiece construction. Single-piece units are completely factory wired, piped and charged, ready for installation. Units use Puron (R-410A) refrigerant and have EERs (Energy Efficiency Ratio) up to 14.6. Units include a direct expansion evaporator coil, compressors, and water-cooled cleanable condensers. The VAV units include a single or multiple belt drive evaporator fan(s) with VFD (variable frequency drive) controlled motor and complete microprocessor control system. Optional water economizers and hot water heating may also be added. 50BVT,V,W,Z034-064 MODULAR OMNIZONE UNIT © Carrier Corporation 2013

Open the catalog to page 1
OMNIZONE™ 50BV020-064 - 2

Features/Benefits (cont) These vertical package units offer flexible economical air conditioning for today’s office environment. Compressors are mounted on vibration isolators. Each compressor is equipped with a coaxial tube-in-tube condenser for maximum heat transfer efficiency and performance. All condensers are rated at 600 psig operating refrigerant pressures and 400 psig water-side pressures. Evaporators are enhanced fin, rifled tube type for maximum performance. Large face areas ensure low airside pressure drops and reduced face velocities to prevent condensate carry over and maximum...

Open the catalog to page 2
OMNIZONE™ 50BV020-064 - 3

Model number nomenclature 5 0 B V Model Series 50BV – OMNIZONE Indoor SelfContained Unit Unit Type C – (CV) Cool Only, W/C, Single Piece* J – (VAV) Cool Only, W/C, Single Piece*† Q – (CV) Heat Pump, W/C, Single Piece T – (CV) Cool Only, W/C, Modular V – (CV) Heat Pump, W/C, Modular W – (VAV) Cool Only, W/C, Modular Y – (VAV) Heat Pump, Single Piece† Z – (VAV) Heat Pump, Modular Economizer and Hot Gas Reheat Options - – None A – Water Economizer with 3-Way Valve Package and Controls B – Water Economizer with Field-Supplied Valves and Controls C – Cycling Hot Gas Reheat Coil D – Cycling Hot...

Open the catalog to page 3
OMNIZONE™ 50BV020-064 - 4

AHRI* capacity ratings UNIT 50BVC LEGEND EER — Energy Efficiency Ratio *AHRI — Air Conditioning, Heating, and Refrigeration Institute. R-410A unit rating. NOTE: Units rated in accordance with AHRI 340/360 conditions.

Open the catalog to page 4
OMNIZONE™ 50BV020-064 - 5

Physical data — 50BVC,J,Q,Y units UNIT 50BVC,J,Q,Y NOMINAL CAPACITY (Tons) SHIPPING WEIGHT (lb) 50BVC,Q…50BVJ,Y* COMPRESSOR Quantity Number of Refrigerant Circuits Oil (oz) Ckt 1…Ckt 2 REFRIGERANT TYPE Expansion Device Operating Charge (lb) Ckt 1…Ckt 2 CONDENSER (50BVC,Q,J only) Quantity of Manifolded Circuits Nominal Flow Rate (Gpm) Water Flow Range (Gpm) Max Water Working Pressure (psig) Max Refrig Working Pressure (psig) Min Entering Water Temp (F) Max Entering Water Temp (F) Waterside Volume (Gal.) EVAPORATOR COIL Rows…Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity…Size Type...

Open the catalog to page 5
OMNIZONE™ 50BV020-064 - 6

Physical data — 50BVT,V,W,Z units UNIT 50BVT,V,W,Z NOMINAL CAPACITY (Tons) SHIPPING WEIGHT (lb) 50BVT,V…50BVW,Z COMPRESSOR Quantity Number of Refrigerant Circuits Oil (oz) Circuit 1…Circuit 2 Circuit 3…Circuit 4 REFRIGERANT TYPE Expansion Device Operating Charge (lb) Circuit 1…Circuit 2 Circuit 3…Circuit 4 CONDENSER (50BVT,V,W only) Quantity of Manifolded Circuits Nominal Flow Rate (Gpm) Water Flow Range (Gpm) Max Water Working Pressure (psig) Max Refrig Working Pressure (psig) Min Entering Water Temp (F) Max Entering Water Temp (F) Waterside Volume (Gal.) WATERSIDE ECONOMIZER COIL...

Open the catalog to page 6
OMNIZONE™ 50BV020-064 - 7

Factory-installed options Waterside economizer — A condenser water pre-cooling coil located before the direct expansion cooling coils allows the use of the condenser water to provide free cooling. When the condenser water temperature is less than an adjustable set point or more below the return-air temperature, condenser water is directed to the economizer coil to obtain free cooling. When free cooling is available the economizer coil functions as the first stage of cooling. The economizer coil valve can be modulated to control discharge-air temperature when the economizer can meet or...

Open the catalog to page 7
OMNIZONE™ 50BV020-064 - 8

FRONT RETURN. TOP SUPPLY LEFTSIDE VIEW RIGHT SIDE VIEW

Open the catalog to page 8
OMNIZONE™ 50BV020-064 - 9

BLOWER SECTION ACCESS BLOWER SECTION ACCESS STANDARD DISCHARGE EVAPORATOR ACCESS COMPRESSOR ACCESS LIFTING SUPPORT RAIL REAR VIEW RETURN AIR VIEW LEFT SIDE VIEW EVAPORATOR ACCESS REAR DISCHARGE (Optional) EVAPORATOR ACCESS EVAPORATOR ACCESS FILTER ACCESS ECONO COIL (Optional) DIRECT EXPANSION EVAPORATOR REHEAT COIL (Optional) BLOWER SECTION ACCESS COMPRESSOR ACCESS WATER IN (ECONO COIL OPTIONAL) FRONT VIEW B LEFT SIDE VIEW NOTES: 1. Dimensions in inches [mm]. 2. All units are rear return airflow configuration. 3. Constant volume units are available with front or rear air supply 4....

Open the catalog to page 9
OMNIZONE™ 50BV020-064 - 10

Dimensions (cont) "SHIPPING SECTION" LIFTING SUPPORT RAIL REAR VIEW LEFT SIDE VIEW ECONO COIL (OPTIONAL) - DIRECT EXPANSION EVAPORATOR - REHEAT COIL (OPTIONAL) - ECONO COIL (OPTIONAL) - DIRECT EXPANSION EVAPORATOR - REHEAT COIL (OPTIONAL)- (ECONO COIL- LEFT SIDE VIEW REPLACEMENT FILTERS : EIGHT (8) AT 17 x 27 x 4 INCHES. 2. All units are rear return airflow configuration. 3. Recommended minimum service clearances are as follows: b. Left or right side — 65 [1651] for coil removal c. Side opposite coil removal — 20 [508] FRONT DISCHARGE

Open the catalog to page 10