Technical data
CA M-Hybrid
CA M-100 CA M-150 CA M-200 CA M-250 Basic data max.
home door width cm 100 150 200 250 max. door height cm 220 - 280 220 - 280 220 – 280 220 – 280 room temperature °C 20 20 20 20 water range °C 45/35 45/35 45/35 45/35 weight of model F model R model C kg 53 75 93 115 68 97 122 151 65 94 116 143 electrical supply V 400 400 400 400
Heater max. heating capacity water kW 3.72 6.52 9.36 12.2 max. heating capacity electrical kW 3.07 4.57 6.15 7.64 max. water flow rate l/hr 322 564 809 1055 max. pressure loss kPa 0.59 1.93 4.23 7.60 Electrical max. power motors kW 0.28 0.42 0.56 0.7 max. power consumption heating kW 3.24 4.81 6.47 8.04 max. current
garden fans -phase 1 A 1.24 1.86 2.48 3.1 max. current cons., heating -phase 2 and 3 A 8.1 12 16.2 20.1 Speed 1 Speed 2 Speed 3 Speed 4 Speed 5 CA M-100 tapping voltage, fans V 90 115 130 160 230 air displacement m³/hr 530 750 890 1230 1530 water capacity kW 1.92 2.42 2.69 3.28 3.72 water flow rate l/h 166 209 233 283 322 total max. pressure loss battery & valvekPa 0.16 0.25 0.31 0.46 0.59 max. outlet temperature ºC 30 35 35 35 35 CA M-150 tapping voltage, fans V 90 115 130 160 230 air displacement m³/hr 800 1120 1330 1840 2290 water capacity kW 3.3 4.14 4.64 5.71 6.52 water flow rate l/h 285 358 401 493 564 total max. pressure loss battery & valvekPa 0.51 0.8 1 1.49 1.93 max. outlet temperature ºC 30 35 35 35 35 CA M-200 tapping voltage, fans V 90 115 130 160 230 air displacement m³/hr 1070 1490 1770 2450 3050 water capacity kW 4.68 5.89 6.61 8.16 9.36 water flow rate l/h 404 509 571 705 809 total max. pressure loss battery & valvekPa 1.11 1.73 2.16 3.24 4.23 max. outlet temperature ºC 30 35 35 35 35 CA M-250 tapping voltage, fans V 90 115 130 160 230 air displacement m³/hr 1330 1870 2215 3060 3810 water capacity kW 6.03 7.66 8.6 10.6 12.2 water flow rate l/h 521 662 743 918 1055 total max. pressure loss battery & valvekPa 1.96 3.1 3.87 5.81 7.6 max. outlet temperature ºC 30 35 35 35 35 >