Catalogue Uniset E1 CO Detection & Control Unit
www.acmeprod.com
print switch display
Page / 2
Acme Engineering Products, Inc. - 110055
/ 2
See other catalogues for Acme Engineering Products, Inc.
Text version of the page

Technical Data:01-01E1R : UniSet E1 CO Detector CO Sensor/TransmitterModel No.: CO-STE3 CO DetectorModel No.: 01-01E3RTypical Wiring Diagram

Gas detected:Carbon MonoxideDetection range:0-200 PPM Sensor:N-type Metal Oxide SemiconductorFor remote sensor, order model #01-01E1REMounting:Wall or column with brackets (supplied) Unit dimensions (mm):152mmH x 152mmW x 101mmD (6”H x 6”W x 4”D)Supply voltage:120V 50-60 Hz,15VA (available 24V or 220 VAC)Number of Relay Outputs:1 SPDT or 2 SPDT (01-01E1R+ Option) Contact rating:3A 120V AC 1PHContact relay output :Selectable PPM level (0-200)LED indicators:Power On, Low Level, High Level Audible alarm:Electronic buzzer at selectable PPM level.Table of other ACME Single Point Carbon Monoxide (CO) Detection Units.

Principle of Operation:

The UniSet E1 CO detection unit employsan N-type Metal Oxide Semiconductor sensor.An on-board hybrid microprocessor stabilizesthe response of the sensor by alternating its heater current (low current and high current). During the "high current" period, water vapor and other miscellaneous gases are removed from the sensor element's surface thus enhancing its sensitivity and repeatability characteristics. At an optimum moment close to the end of the "low current" period the output of the sensor is read by the microprocessor and its value is stored in memory. This cycle is repeated every one second. The stored sensor output value is updated at each "low current" to "high current" transition.The stored output value of the sensor iscompared against the two pre-calibrated "LOW" and "HIGH" CO alarm threshold values and when found exceeding these levels the respective CO status LED indicators on the unit cover are energized.The UniSet E1 has an on-board output relayand an alarm buzzer that can be independently configured to energize at different CO levels. The standard factory configuration is as follows : output relay energizes at the "LOW" CO alarm level and alarm buzzer energizes at the "HIGH" CO alarm level. To alter the configuration please refer to the operating manual of the unit.The UniSet E1 uses a thermistor in the sensorbridge circuit in order to minimize the sensor dependency on ambient temperature and humidity variations. MODEL 01-01E1R+-120SPDTRELAY OUTPUT CONTACTRATING: 3A @ 120V AC

L N4 5 6 1 2 3

120V AC 50-60Hz,DEDICTATED CIRCUIT

In the U.S.A.

Trimex Ind. Bldg., PMB #10 2330 State Route 11 Mooers, N.Y. 12958 Tel. : (518) 236-5659 Fax : (518) 236-6941

In Canada

Represented by: 3 or 4 fixed contact levels, plus time delay alarm level with audible alarm.Wall-mounted enclosure, dimensions (mm) 152H x 152W x 101D.For unit with remote sensor order model #01-01E3RE.4-20 mA analog output, no contacts.Wall-mounted enclosure, dimensions (mm) 152H x 152W x 101D. ACME ENGINEERING PROD. INC. ACME ENGINEERING PROD. LTD. 5706 Royalmount Ave., Montreal, Quebec H4P 1K5 Tel. : (514) 342-5656 Fax : (514) 342-3131

E-mail : info@acmeprod.com - Internet : www.acmeprod.com

The information provided by this bulletin is a general description of ACME UNITS. All specifications are subject to change without notice.Installation, maintenance and other instructions provided with the equipment shall be closely followed by installers, owners and users.