| | | SA/S 4.6.1 8.6.1 12.6.1 | SA/S 2.10.1 4.10.1 8.10.1 12.10.1 | SA/S 2.16.1 4.16.1 8.16.1 12.16.1 | SA/S 2.16.5S 4.16.5S 8.16.5S 12.16.5 | SA/S 2.20.1S 4.20.1S 8.20.1S 12.20.1 | |
| | Type of installation | MDRC | MDRC | MDRC | MDRC | MDRC | |
| | Rate Current In / A | 6A | 10AX | 16A | 16AX C-Load | 20AX | |
| | Current detection | - | - | - | ■ | ■ | |
| | Operating Voltage necessary | no | no | no | no | no | |
| | Functions | | | | | | |
| | Number of Application programs | 1 | 1 | 1 | 1 | 1 | |
| | Switch function | | | | | | |
| | - ON delay | ■ | ■ | ■ | ■ | ■ | |
| | - OFF delay | ■ | ■ | ■ | ■ | ■ | |
| | | ■ | ■ | ■ | ■ | ■ | |
| | - Warning before end of staircase lighting | ■ | ■ | ■ | ■ | ■ | |
| | - Staircase lighting time set over object | ■ | ■ | ■ | ■ | ■ | |
| | - Flashing | ■ | ■ | ■ | ■ | ■ | |
| | - Switch response can be set | ■ | ■ | ■ | ■ | ■ | |
| | - Threshold | ■ | ■ | ■ | ■ | ■ | |
| | Current detection | | | | | | |
| | - Threshold | | | | ■1) | ■ | |
| | - Current values | | | | ■1) | ■ | |
| | Scene function | ■ | ■ | ■ | ■ | ■ | |
| | Logic function | | | | | | |
| | - Logic object AND | ■ | ■ | ■ | ■ | ■ | |
| | - Logic object OR | ■ | ■ | ■ | ■ | ■ | |
| | - Logic object XOR | ■ | ■ | ■ | ■ | ■ | |
| | | ■ | ■ | ■ | ■ | ■ | |
| | Priority object (positive drive) | ■ | ■ | ■ | ■ | ■ | |
| | Heating actuator | | | | | | |
| | - Switch ON/OFF (two-step) | ■ | ■ | ■ | ■ | ■ | |
| | - Continuous control (PWM) | ■ | ■ | ■ | ■ | ■ | |
| | - Cyclical fault monitoring | ■ | ■ | ■ | ■ | ■ | |
| | - Automatic purging | ■ | ■ | ■ | ■ | ■ | |
| | | | | | | | |
| | Special function | | | | | | |
| | - Default position on bus voltage failure | ■ | ■ | ■ | ■ | ■ | |
| | - Status response object | ■ | ■ | ■ | ■ | ■ | |
| | Switching of loads and breaking capacity | | | | | | |
| | Switching load acc. AC1 EN 60947-4-1 AC3 | 6 A 6 A | 10 A 8 A | 16 A | 16 A 16 A | 20 A 16 A | |
| | Switching load acc. EN60669 | 6 A (35 uF) | 10 AX (140 uF) | 16 A (70 uF) | 16 AX (200 uF) | 20 AX (140 uF) | |
| | Mechanical contact endurance | 107 | 3x106 | 3x106 | 106 | 106 | |
| | Electrical endurance acc. IEC 60947-4-1 Rate current In - AC1 (240V/0.8) Rate current In - AC3 (240V/0.45) Rate current In - AC5a (240V/0.45) | 100.000 30.000 30.000 | 100.000 30.000 30.000 | 100.000 30.000 30.000 | 100.000 30.000 30.000 | 100.000 30.000 30.000 | |
| | Incandescent bulbs | 1200 W | 2300 W | 2500 W | 3680 W | 3680 W | |
| | | 800 W 300 W 350 W | 2300 W 1500 W 1500 W | 2500 W 1500 W 1500 W | 3680 W 2500 W 3680 W | 3680 W 2500 W 3680 W | |
| | | 800 W 1000 W | 1200 W 1500 W | 1200 W 1500 W | 2000 W 2500 W | 2000 W 2500 W | |
| | | 1000 W | 2300 W | 2500 W | 3680 W | 3680 W | |
| | Duluxlampen (Energy saving lamps) Uncompensated Parallel compensated | 800 W 800 W | 1100 W 1100 W | 1100 W 1100 W | 3680 W 3000 W | 3680 W 3000 W | |
| | Vapour lamps Uncompensated Parallel compensated | 1000 W 800 W | 2000 W 2000 W | 2000 W 2000 W | 3680 W 3000 W | 3680 W 3000 W | |
| | Max. Peak Current (150 us) (250 us) | 200 A 160 A | 400 A 320 A | 400 A 320 A | 600 A 480 A | 600 A 480 A | |
| | Number of Electronic ballasts (T5/T8) | | | | | | |
| | 18 W (ABB EVG 1x18 CF) | 10 | 23 | 23 | 262) | 262) | |
| | 24 W (ABB EVG-T5 1x24 C) | 10 | 23 | 23 | 262) | 262) | |
| | 36 W (ABB EVG 1x36 CF) | 7 | 14 | 14 | 22 | 22 | |
| | 58 W (ABB EVG 1x58 CF) | 5 | 11 | 11 | 122) | 122) | |
| | 80 W (HELVA EL 1x80 SC) | 3 | 10 | 10 | 102) | 102) | |
| | | | | | | | |